Give step-by-step solution with explanation and final answer:
What minimum size THHN copper secondary conductors are permitted for a 45kVA, 3-phase, 480V primary and a 208/120V secondary transformer that supplies secondary conductors with a length of 10 feet and terminates in a panelboard with a single 3 - pole circuit breaker rated 150 amperes? Assume all equipment terminations are rated 75°C.
Question:
Give step-by-step solution with explanation and final answer:
What minimum size THHN copper secondary conductors are permitted for a 45kVA, 3-phase, 480V primary and a 208/120V secondary transformer that supplies secondary conductors with a length of 10 feet and terminates in a panelboard with a single 3 - pole circuit breaker rated 150 amperes? Assume all equipment terminations are rated 75°C.
This is AI generated Response.
Asked by: ravi
Created at: 2025-08-18 05:43:21
Final Answer:
RenderedRaw Text
Did you like this answer?
Let's break down the problem step-by-step:
### **Given:**
- **Transformer size:** 45 kVA, 3-phase
- **Primary voltage:** 480V
- **Secondary voltage:** 208/120V (we'll use 208V, the line-to-line voltage)
- **Secondary conductor length:** 10 feet
- **Termination:** Panelboard with **one 3-pole breaker, 150A**
- **Conductor type:** THHN copper
- **Termination temperature rating:** 75°C
---
## **Step 1: Calculate the Full Load Current on the Secondary Side**
The formula for 3-phase current is:
\[
I = \frac{\text{Transformer kVA} \times 1000}{\sqrt{3} \times \text{Voltage}}
\]
Plug in the values:
\[
I = \frac{45,000}{\sqrt{3} \times 208}
\]
\[
I = \frac{45,000}{360.8}
\]
\[
I ≈ 124.7 \text{ A}
\]
---
## **Step 2: Determine the Minimum Conductor Ampacity Required**
### **NEC 240.21(C) – Protection of Transformer Secondary Conductors**
For secondary conductors **not over 10 feet long**, you can use the "10-foot tap rule." The requirements for this rule include:
- The ampacity of the secondary conductor is **not less than the combined calculated loads on the circuits supplied by the tap conductors**.
- The tap conductors **terminate in a single circuit breaker** (which they do: a 150A breaker).
- The ampacity of the secondary conductor **is not less than 1/10th of the rating of the overcurrent device**, but this is a minimum.
**But** the conductors must always be sized for at least the load they serve.
### **What ampacity do we need?**
- **Load on the transformer:** 124.7A (from Step 1)
- **Breaker size:** 150A
**Per the 10-foot tap rule** (NEC 240.21(C)(2)), the conductors must have an ampacity **not less than the load** (124.7A), and **not less than the rating of the breaker** if the tap conductors terminate in a single breaker (as here).
**So, the conductors must be rated for at least 124.7A.**
---
## **Step 3: Select the Conductor Size Using NEC Table 310.16 (2023) [or 310.15(B)(16) in previous NECs]**
**THHN copper at 75°C:**
- **1 AWG:** 130A
- **2 AWG:** 115A
- **1/0 AWG:** 150A
- **Our load:** 124.7A
So, **2 AWG** is only good for 115A (not enough).
**1 AWG** is good for 130A (meets the requirement).
**1/0 AWG** is good for 150A (more than needed).
---
## **Step 4: Final Check – Does 1 AWG Meet All Rules?**
- **Ampacity:** 130A (1 AWG), which is **greater than 124.7A**.
- **Breaker:** 150A – per 240.21(C)(2), the tap can terminate in a single breaker rated no more than the ampacity of the conductors, which in this case is **not more than 10x the ampacity of the conductors**. 150A/130A = 1.15 (so it's less than 10x).
- **Length:** 10 feet or less.
- **Termination:** Single breaker.
**All requirements satisfied.**
---
## **Step 5: Final Answer**
### **The minimum size THHN copper secondary conductors permitted for this transformer installation is:**
\[
\boxed{1 \text{ AWG} \ \text{THHN copper}}
\]
at 75°C ampacity (130A).
---
### **Summary Table**
| Conductor Size | 75°C Ampacity (THHN Cu) | Sufficient? |
|----------------|------------------------|-------------|
| 2 AWG | 115A | **No** |
| 1 AWG | 130A | **Yes** |
| 1/0 AWG | 150A | Yes |
---
### **References:**
- NEC Table 310.16 (2023) / 310.15(B)(16) (older editions)
- NEC 240.21(C)(2) – 10-foot tap rule
---
**Final Answer:**
\[
\boxed{\text{1 AWG THHN copper}}
\]
is the minimum size permitted for the secondary conductors in this scenario.
Question:
fasdfasf
This is AI generated Response.
Asked by: Vishal
Created at: 2025-09-11 18:35:59
Final Answer:
RenderedRaw Text
Did you like this answer?
# Minimum Size THHN Copper Secondary Conductors Calculation
## **Given:**
- **Transformer Size:** 45 kVA, 3-phase
- **Primary Voltage:** 480V
- **Secondary Voltage:** 208/120V (using 208V)
- **Length of Secondary Conductors:** 10 feet
- **Termination:** Panelboard with a 3-pole breaker rated at 150A
- **Conductor Type:** THHN copper
- **Temperature Rating:** 75°C
---
## **Step 1: Calculate Full Load Current on Secondary Side**
Use the formula for 3-phase current:
\[
I = \frac{\text{Transformer kVA} \times 1000}{\sqrt{3} \times \text{Voltage}}
\]
Calculating:
\[
I = \frac{45,000}{\sqrt{3} \times 208} \approx \frac{45,000}{360.8} \approx 124.7 \text{ A}
\]
---
## **Step 2: Determine Minimum Conductor Ampacity Required**
### **NEC 240.21(C) – Protection of Transformer Secondary Conductors**
- For conductors **not over 10 feet long**, apply the "10-foot tap rule."
- Ampacity of the secondary conductor must not be less than the calculated load (124.7A) or the rating of the breaker (150A).
### **Load vs. Breaker:**
- **Calculated Load:** 124.7A
- **Breaker Size:** 150A
The conductors must meet the higher of these two values.
---
## **Step 3: Select Conductor Size from NEC Table 310.16**
### **THHN Copper at 75°C:**
| Conductor Size | 75°C Ampacity |
|----------------|----------------|
| 2 AWG | 115A |
| 1 AWG | 130A |
| 1/0 AWG | 150A |
- **2 AWG:** 115A (not sufficient)
- **1 AWG:** 130A (sufficient)
- **1/0 AWG:** 150A (exceeds requirement)
---
## **Step 4: Final Check for 1 AWG**
- **Ampacity of 1 AWG:** 130A (greater than 124.7A)
- **Breaker Rating:** 150A – meets the requirement of terminating at a single breaker.
- **Length:** 10 feet or less.
- **Termination:** Single breaker.
All requirements are satisfied.
---
## **Final Answer**
### **The minimum size THHN copper secondary conductors permitted for this transformer installation is:**
\[
\boxed{1 \text{ AWG} \ \text{THHN copper}}
\]
---
### **Summary Table**
| Conductor Size | 75°C Ampacity (THHN Cu) | Sufficient? |
|----------------|--------------------------|-------------|
| 2 AWG | 115A | No |
| 1 AWG | 130A | Yes |
| 1/0 AWG | 150A | Yes |
---
### **References:**
- NEC Table 310.16 (2023) / 310.15(B)(16) (older editions)
- NEC 240.21(C)(2) – 10-foot tap rule
---
**Final Answer:**
\[
\boxed{\text{1 AWG THHN copper}}
\]
is the minimum size permitted for the secondary conductors in this scenario.
VIPSolutions focuses on clear, step‑by‑step explanations so you can learn quickly. Whether you need an AI‑generated walkthrough or a short hint to get unstuck, each solution is organized for fast reading and easy review later.
Search similar questions, compare approaches, and bookmark the best answers for revision. Our goal is simple: quick, reliable study help that feels natural—not noisy.