Give step-by-step solution with explanation and final answer: What maximum standard size primary OCPD is permitted to protect the secondary conductors of a 2 - wire 480V primary 120V secondary, single phase transformer when the secondary conductor is a 1/0 THW copper? Assume all equipment terminations are rated 75°C. Indicate your answer by inputting only the number corresponding to your answer in the box provided.

Question:

Give step-by-step solution with explanation and final answer: What maximum standard size primary OCPD is permitted to protect the secondary conductors of a 2 - wire 480V primary 120V secondary, single phase transformer when the secondary conductor is a 1/0 THW copper? Assume all equipment terminations are rated 75°C. Indicate your answer by inputting only the number corresponding to your answer in the box provided.

This is AI generated Response.
Asked by: ravi
Created at: 2025-08-18 05:50:29

Final Answer:

Rendered Raw Text
Did you like this answer?
Let's break down the problem step by step: **Given:** - Single phase transformer - 2-wire 480V primary, 120V secondary - Secondary conductor: 1/0 AWG THW copper - Terminations rated 75°C - Need to determine the **maximum standard size primary OCPD** allowed to protect the **secondary conductors**. --- ## Step 1: Find the ampacity of 1/0 AWG THW copper at 75°C From **NEC Table 310.16 (2023)**: - 1/0 AWG copper, 75°C column = **150 amps** --- ## Step 2: Determine the maximum allowed OCPD for secondary conductors **Per NEC 240.4(B):** - Next higher standard OCPD is allowed if the ampacity does not correspond to a standard OCPD size and if certain conditions are met. **Per NEC 240.6(A):** - Standard sizes: 100, 110, 125, 150, 175, 200, etc. **Per NEC 240.21(C):** - For transformer secondary conductors, the OCPD shall **not exceed the ampacity of the conductor**. --- ## Step 3: Apply the "next higher size" rule Ampacity = 150A Standard OCPD sizes above and below 150A: 125A, **150A**, 175A. Since **150A is a standard size**, and matches the ampacity, **the maximum standard size OCPD is 150A**. --- ## Step 4: Final Answer **Final Answer:** **150** --- ## **Summary Table** | Conductor Size | Ampacity (75°C) | Max Standard OCPD | |----------------|------------------|-------------------| | 1/0 AWG THW Cu | 150A | **150A** | --- **Input only the number:** **150**

📢 Instructions:

  • Ask anything relatd to above question only.
  • For new Question goto :

Study Help, Fast Answers

VIPSolutions focuses on clear, step‑by‑step explanations so you can learn quickly. Whether you need an AI‑generated walkthrough or a short hint to get unstuck, each solution is organized for fast reading and easy review later.

Search similar questions, compare approaches, and bookmark the best answers for revision. Our goal is simple: quick, reliable study help that feels natural—not noisy.