Give step-by-step solution with explanation and final answer:
1
-
A
4
-
story wooden frame building has each floor of area
5
0
9
m
2
.
This building is adjacent to a
5
story building of ordinary construction with
9
0
0
m
2
per floor. Determine the fire flow and duration for each building and that for both buildings
(
assuming that they are connected
)
.
2
-
Estimate the water requirements for a community that will reach a population of
1
2
0
0
0
0
at the design year. The estimated municipal water demand for the community is
6
1
0
Lepd
.
Calculate fire flow, design capacity of the water treatment plant, and design capacity of the water distribution system. Use NBFU formula for fire flow.
Question:
Give step-by-step solution with explanation and final answer:
1
-
A
4
-
story wooden frame building has each floor of area
5
0
9
m
2
.
This building is adjacent to a
5
story building of ordinary construction with
9
0
0
m
2
per floor. Determine the fire flow and duration for each building and that for both buildings
(
assuming that they are connected
)
.
2
-
Estimate the water requirements for a community that will reach a population of
1
2
0
0
0
0
at the design year. The estimated municipal water demand for the community is
6
1
0
Lepd
.
Calculate fire flow, design capacity of the water treatment plant, and design capacity of the water distribution system. Use NBFU formula for fire flow.
This is AI generated Response.
Asked by: VARRI NAVEEN
Created at: 2025-10-26 19:48:26
Final Answer:
RenderedRaw Text
Did you like this answer?
# Problem 1: Fire Flow and Duration for Two Adj Buildings
## Given Data:
### Building 1 (Wooden Frame)
- Number of floors: 4
- Area per floor: 509 m²
Building 2 (Ordinary Construction)
- Number of floors: 5
- Area per floor: 900 m²
---
## Step 1: Calculate the fire flow for each building
### Fire flow formula (assuming the **National Building Fire Use (NBFU)** method):
\[
Q = \text{Area} \times \text{Fire flow factor}
\]
*Note: For typical calculations, the fire flow factor varies based on construction type. For simplicity, assume standard factors:*
- Wooden buildings: **.2 L/s per m²**
- Ordinary construction: **.4 L/s per m²**
---
### Fire flow for Building 1 (Wooden Frame):
\[
Q_1 = 509 \text{ m}^2 \times 4 \text{ floors} \times .2 \text{ L/s per m}^2
\]
\[
Q_1 = 509 \times 4 \times .2 = 407.2 \text{ L/s}
\]
---
### Fire flow for Building 2 (Ordinary Construction):
\[
Q_2 = 900 \text{ m}^2 \times 5 \text{ floors} \times .4 \text{ L/s per m}^2
\]
\[
Q_2 = 900 \times 5 \times .4 = 180 \text{ L/s}
\]
---
## Step 2: Determine fire flow for both buildings connected
- When connected, the **total fire flow** is the **sum** of individual flows:
\[
Q_{total} = Q_1 + Q_2 = 407.2 + 180 = \boxed{2207.2 \text{ L/s}}
\]
---
## Step 3: Estimate fire duration
- Assume a typical fire duration of **2 hours** (or 720 seconds).
- The **total water requirement**:
\[
W = Q_{total} \times \text{duration}
\]
\[
W = 2207.2 \text{ L/s} \times 720 \text{ s} = 15,887,040 \text{ L}
\]
---
# **Final Summary for Problem 1:**
| Quantity | Building 1 | Building 2 | Both Connected |
|---|---|---|---|
| Fire flow (L/s) | 407.2 | 180 | 2207.2 |
| Fire duration | 2 hours | 2 hours | 2 hours |
| Total water (L) | 2,927,424 | 12,959,616 | 15,887,040 |
---
# Problem 2: Water Requirements for a Community
## Given Data:
- Population at design year: **1,200,000**
- Municipal water demand: **610 Lpd (Liters per capita per day)**
- Community population: **1,200,000**
---
## Step 1: Calculate total water demand
\[
Q_{demand} = \text{Population} \times \text{Water demand per capita}
\]
\[
Q_{demand} = 1,200,000 \times 610 \text{ Lpd}
\]
\[
Q_{demand} = 732,000,000 \text{ L}
\]
---
## Step 2: Convert to **L/sec** for design capacity
\[
Q_{sec} = \frac{732,000,000}{24 \times 360} = \frac{732,000,000}{86,400} \approx 8,472 \text{ L/sec}
\]
---
## Step 3: Fire flow estimation using **NBFU formula**
\[
Q_f = .2 \times \sqrt{A}
\]
Where \(A\) is the **area** of the community or a representative zone. Since no specific area is given, assume the **fire flow** is proportional to the total water demand.
**Alternatively**, based on standard practice, a **fire flow** of at least **3,600 L/min (60 L/sec)** is often used for large communities.
---
## Step 4: Design capacity of water treatment plant
- To meet **daily demand**:
\[
Q_{plant} = 8,472 \text{ L/sec}
\]
- **Design capacity** should include a **peak factor**, typically 2:
\[
Q_{design} = 2 \times 8,472 = 16,944 \text{ L/sec}
\]
---
## Step 5: Design capacity of water distribution system
- The **distribution system capacity** should accommodate both **average demand** and **fire flows**.
- Given the **fire flow** estimated at **3,600 L/min (60 L/sec)**, the **system capacity**:
\[
Q_{system} = \max(Q_{demand}, Q_{fire})
\]
\[
Q_{system} \approx \max(8,472 \text{ L/sec}, 60 \text{ L/sec})
\]
- Since fire flow is small compared to demand, the **distribution system** should be designed for **at least 16,944 L/sec**.
---
# **Final Summary for Problem 2:**
| Quantity | Estimated Value |
|---|---|
| Total water demand | 732 million L/day |
| Water treatment plant capacity | ~16,944 L/sec |
| Water distribution system capacity | ~16,944 L/sec |
| Estimated fire flow | ~3,600 L/min (60 L/sec) |
---
# **Key Assumptions:**
- Fire flow factors are based on standard values.
- Fire duration is 2 hours for calculation.
- Peak factors are applied to demand for capacity estimation.
- Fire flow and water demands are approximated proportionally.
---
**End of Solution**
VIPSolutions focuses on clear, step‑by‑step explanations so you can learn quickly. Whether you need an AI‑generated walkthrough or a short hint to get unstuck, each solution is organized for fast reading and easy review later.
Search similar questions, compare approaches, and bookmark the best answers for revision. Our goal is simple: quick, reliable study help that feels natural—not noisy.