VIPSolutions logo ✨ VIPSolutions

Give step-by-step solution with explanation and final answer: An industrial plant is supplied by 5 0 0 ft , three - wire, 4 8 0 V , three - phase feeder. The load of the plant is 2 5 0 kVA with a power factor of 0 . 9 0 . Determine: ( a ) The size of the feeder and conduit using THW copper conductors. ( b ) The voltage drop in the feeder ( Assume a steel conduit ) . ( c ) The stze of the feeder and conduit that limit the voltage drop to 1 % .

Question:

Give step-by-step solution with explanation and final answer: An industrial plant is supplied by 5 0 0 ft , three - wire, 4 8 0 V , three - phase feeder. The load of the plant is 2 5 0 kVA with a power factor of 0 . 9 0 . Determine: ( a ) The size of the feeder and conduit using THW copper conductors. ( b ) The voltage drop in the feeder ( Assume a steel conduit ) . ( c ) The stze of the feeder and conduit that limit the voltage drop to 1 % .

This is AI generated Response.
Asked by: Aman
Created at: 2025-11-13 08:39:55

Final Answer:

Rendered Raw Text
Did you like this answer?
# Step-by-Step Solution ## Given Data - **Distance (Length of feeder)**, \( L = 500 \) ft - **System type:** 3-wire, 480 V, 3-phase - **Load:** \( = 250) kVA- **Power:** \( pf = .90 \) (lagging) - **Conductor type:** THW copper - **Conduit:** Assume steel - **Tasks:** (a) Feeder and conduit size for ampacity (b) Voltage drop in feeder (c) Feeder and conduit size for max 1% voltage drop --- ## (a) Feeder and Conduit Size (Ampacity) ### 1. Calculate Full-Load Current The three-phase current is: \[ I = \frac{S}{\sqrt{3} \cdot V \cdot pf} \] But \( S \) is *apparent* power, so: \[ I = \frac{S}{\sqrt{3} \cdot V} \] \[ I = \frac{250,000}{\sqrt{3} \times 480} \] \[ I = \frac{250,000}{831.8} \] \[ I \approx 300.5 \text{ A} \] ### 2. Feeder Ampacity Selection Per NEC, feeders should be sized for 125% of continuous load (unless otherwise specified): \[ I_\text{feeder} = 1.25 \times 300.5 = 375.6 \text{ A} \] ### 3. Select THW Copper Conductor Size From NEC Table 310.16 (2023): - **THW Copper @ 75°C:** - 500 kcmil: 380 A - 400 kcmil: 335 A - 350 kcmil: 310 A **Select:** - **500 kcmil THW copper** (ampacity 380 A) ### 4. Conduit Size Per NEC Chapter 9, Table 5 (for THW insulation): - **500 kcmil THW copper:** .707 in² per wire Three wires needed for 3-phase, 3-wire: \[ 3 \times .707 = 2.121 \text{ in}^2 \] NEC Table 4 (conduit fill, 40% max for 3 conductors): - **3" Trade Size RMC (Rigid Metal Conduit):** 2.864 in² (40% fill) **Select:** - **3" RMC steel conduit** --- ### **Summary (a)** - **Feeder:** 3 × 500 kcmil THW copper - **Conduit:** 3" RMC steel --- ## (b) Voltage Drop in the Feeder ### 1. Use Voltage Drop Formula (Three-Phase, Balanced Load) \[ \Delta V = \sqrt{3} \cdot I \cdot (R \cos\theta + X \sin\theta) \cdot L \] Where: - \( I = 300.5 \) A (from above) - \( \cos\theta = .90 \), \( \sin\theta = \sqrt{1 - .9^2} = .4359 \) - \( L = 500 \) ft (one-way length) - \( R \) and \( X \) per 100 ft for 500 kcmil THW copper in steel conduit: - **R (resistance):** .022 ohms/100 ft - **X (reactance):** .016 ohms/100 ft ### 2. Calculate Total Resistance and Reactance For 500 ft: \[ R_{500} = .022 \times \frac{500}{100} = .011 \ \Omega \] \[ X_{500} = .016 \times \frac{500}{100} = .008 \ \Omega \] ### 3. Plug Values into Formula \[ \Delta V = \sqrt{3} \times 300.5 \times [.011 \times .90 + .008 \times .4359] \] First, calculate inside the brackets: \[ .011 \times .90 = .0099 \] \[ .008 \times .4359 = .0035 \] \[ .0099 + .0035 = .0134 \] Now, \[ \Delta V = 1.732 \times 300.5 \times .0134 \] \[ = 520.4 \times .0134 \] \[ = 6.97 \text{ V} \] ### 4. Percentage Voltage Drop \[ \text{Percent drop} = \frac{6.97}{480} \times 100\% \] \[ = 1.45\% \] --- ### **Summary (b)** - **Voltage drop:** \( 6.97 \) V (\( 1.45\% \) of 480 V) --- ## (c) Feeder and Conduit Size for 1% (Max) Voltage Drop ### 1. Maximum Allowable Voltage Drop \[ \Delta V_\text{max} = 1\% \times 480V = 4.8 \text{ V} \] ### 2. Rearranged Formula for Resistance & Reactance \[ \Delta V = \sqrt{3} \cdot I \cdot (R \cos\theta + X \sin\theta) \] \[ R \cos\theta + X \sin\theta = \frac{\Delta V}{\sqrt{3} \cdot I} \] Plug in values: \[ \frac{4.8}{1.732 \times 300.5} = \frac{4.8}{520.4} = .00923 \] So, \[ R \cos\theta + X \sin\theta = .00923 \] Recall: \[ R \cos\theta + X \sin\theta = (R_{500}) \cdot .90 + (X_{500}) \cdot .4359 \] Let’s solve for the maximum allowed \( R_{500} \) (assuming \( X_{500} \) is proportional to \( R_{500} \) based on wire size). But, more practically, we can try the next larger standard size: **700 kcmil**. #### Table values for 700 kcmil THW copper in steel conduit: - \( R = .016 \, \Omega/100\,\text{ft} \) - \( X = .013 \, \Omega/100\,\text{ft} \) For 500 ft: - \( R_{500} = .016 \times .5 = .008 \, \Omega \) - \( X_{500} = .013 \times .5 = .0065 \, \Omega \) \[ R \cos\theta + X \sin\theta = .008 \times .90 + .0065 \times .4359 \] \[ = .0072 + .00283 = .01003 \] \[ \Delta V = 1.732 \times 300.5 \times .01003 = 520.4 \times .01003 = 5.22\,\text{V} \] **Still too high. Try 900 kcmil:** - \( R = .0127 \, \Omega/100\,\text{ft} \) - \( X = .011 \, \Omega/100\,\text{ft} \) For 500 ft: - \( R_{500} = .0127 \times .5 = .00635 \, \Omega \) - \( X_{500} = .011 \times .5 = .0055 \, \Omega \) \[ = .00635 \times .90 + .0055 \times .4359 = .005715 + .002397 = .00811 \] \[ \Delta V = 1.732 \times 300.5 \times .00811 = 520.4 \times .00811 = 4.22\,\text{V} \] \[ \frac{4.22}{480} \times 100\% = .88\% \] Now below 1%. ### 3. Conduit Size for 900 kcmil - **900 kcmil THW copper:** 1.27 in² per wire \( 3 \times 1.27 = 3.81 \) in² **4" RMC** (40% fill = 4.214 in²) is appropriate. --- ### **Summary (c)** - **Feeder:** 3 × 900 kcmil THW copper - **Conduit:** 4" RMC steel --- # **Final Answers** ## (a) Feeder and Conduit Size (Ampacity) - **Feeder:** 3 × 500 kcmil THW copper - **Conduit:** 3" RMC steel ## (b) Voltage Drop in the Feeder - **Voltage drop:** 6.97 V (\( 1.45\% \) of 480 V) ## (c) Feeder and Conduit Size for 1% Voltage Drop - **Feeder:** 3 × 900 kcmil THW copper - **Conduit:** 4" RMC steel --- **References:** - NEC Table 310.16 (ampacities) - NEC Chapter 9, Table 5 (conduit fill) - Standard resistance/reactance tables for copper conductors in steel conduit

📢 Instructions:

  • Ask anything relatd to above question only.
  • For new Question goto :

Study Help, Fast Answers

VIPSolutions focuses on clear, step‑by‑step explanations so you can learn quickly. Whether you need an AI‑generated walkthrough or a short hint to get unstuck, each solution is organized for fast reading and easy review later.

Search similar questions, compare approaches, and bookmark the best answers for revision. Our goal is simple: quick, reliable study help that feels natural—not noisy.